Two-layer scheduling scheme for pump stations
dc.contributor.author | Sun, Congcong |
dc.contributor.author | Puig Cayuela, Vicenç |
dc.contributor.author | Cembrano Gennari, Gabriela |
dc.contributor.other | Institut de Robòtica i Informàtica Industrial |
dc.contributor.other | Universitat Politècnica de Catalunya. Departament d'Enginyeria de Sistemes, Automàtica i Informàtica Industrial |
dc.date.accessioned | 2015-09-08T11:31:04Z |
dc.date.issued | 2014 |
dc.identifier.citation | Sun, C., Puig, V., Cembrano, M. Two-layer scheduling scheme for pump stations. A: IEEE International Conference on Control Applications. "IEEE Multi-Conference on Systems and Control (MSC 2014), 8-10 octubre, Antibes (France)". Antibes: Institute of Electrical and Electronics Engineers (IEEE), 2014, p. 1741-1746. |
dc.identifier.isbn | 978-1-4799-7408-5 |
dc.identifier.uri | http://hdl.handle.net/2117/76686 |
dc.description.abstract | In this paper, a two-layer scheduling scheme for pump stations in a water distribution network has been proposed. The upper layer, which works in one-hour sampling time, uses Model Predictive Control (MPC) to produce continuous flow set-points for the lower layer. While in the lower layer, a scheduling algorithm has been used to translate the continuous flow set-points to a discrete (ON-OFF) control operation sequence of the pump stations with the constraints that pump stations should draw the same amount of water as the continuous flow set-points provided by the upper layer. The tuning parameters of such algorithm are the lower layer control sampling period and the number of parallel pumps in the pump station. The proposed method has been tested in the Richmond case study. |
dc.format.extent | 6 p. |
dc.language.iso | eng |
dc.publisher | Institute of Electrical and Electronics Engineers (IEEE) |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/3.0/es/ |
dc.subject | Àrees temàtiques de la UPC::Informàtica::Automàtica i control |
dc.title | Two-layer scheduling scheme for pump stations |
dc.type | Conference report |
dc.contributor.group | Universitat Politècnica de Catalunya. SAC - Sistemes Avançats de Control |
dc.contributor.group | Universitat Politècnica de Catalunya. SIC - Sistemes Intel·ligents de Control |
dc.identifier.doi | 978-1-4799-7408-5/14/$31.00 ©2014 IEEE |
dc.description.peerreviewed | Peer Reviewed |
dc.relation.publisherversion | http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=6981564 |
dc.rights.access | Restricted access - publisher's policy |
local.identifier.drac | 15281490 |
dc.description.version | Postprint (published version) |
dc.relation.projectid | info:eu-repo/grantAgreement/EC/FP7/318556/EU/Efficient Integrated Real-time Monitoring and Control of Drinking Water Networks/EFFINET |
dc.date.lift | 10000-01-01 |
local.citation.author | Sun, C.; Puig, V.; Cembrano, M. |
local.citation.contributor | IEEE International Conference on Control Applications |
local.citation.pubplace | Antibes |
local.citation.publicationName | IEEE Multi-Conference on Systems and Control (MSC 2014), 8-10 octubre, Antibes (France) |
local.citation.startingPage | 1741 |
local.citation.endingPage | 1746 |