Enhanced performance of SVC via using rotor speed deviation signal (RSDS)
Cita com:
hdl:2117/84122
Document typeConference report
Defense date2015
Rights accessOpen Access
All rights reserved. This work is protected by the corresponding intellectual and industrial
property rights. Without prejudice to any existing legal exemptions, reproduction, distribution, public
communication or transformation of this work are prohibited without permission of the copyright holder
Abstract
Transient stability enhancement through using a Static Var Compensator (SVC) and Rotor Speed Deviation Signal (RSDS) of synchronous machine are thoroughly investigated in this paper. Speed deviation signal of generator as a remote signal is sent to SVC in order to achieve more transient stability. Studies are carried out on Kundur's four machine two-area test system which SVC is implemented on midway of transmission system. The simulation results verify the effectiveness of the proposed method to improve rotor angle stability versus different kinds of disturbances scenarios. The standard benchmark model is used for the analysis in the MATLAB/Simulink environment.
CitationGhorbani, H., Monadi, M., Luna, A., Candela, J., Rodriguez, P. Enhanced performance of SVC via using rotor speed deviation signal (RSDS). A: European Conference on Power Electronics and Applications. "17th European Conference on Power Electronics and Applications". Ginebra: 2015, p. 1-8.
ISBN9789075815238
Files | Description | Size | Format | View |
---|---|---|---|---|
Enhanced Perfor ... ation Signal_Postprint.pdf | 4,196Mb | View/Open |