Comparison of simplified models for voltage-source-inverter-fed adjustable-speed drive during voltage sags when the during-event continue mode of operation is active
View/Open
ARTICLE (1,243Mb) (Restricted access)
Request copy
Què és aquest botó?
Aquest botó permet demanar una còpia d'un document restringit a l'autor. Es mostra quan:
- Disposem del correu electrònic de l'autor
- El document té una mida inferior a 20 Mb
- Es tracta d'un document d'accés restringit per decisió de l'autor o d'un document d'accés restringit per política de l'editorial
Cita com:
hdl:2117/24746
Document typeArticle
Defense date2014-11-13
Rights accessRestricted access - publisher's policy
All rights reserved. This work is protected by the corresponding intellectual and industrial
property rights. Without prejudice to any existing legal exemptions, reproduction, distribution, public
communication or transformation of this work are prohibited without permission of the copyright holder
Abstract
Three simplified models for adjustable-speed drives are compared with measurements on an actual drive where the
inverter control strategy remains unaltered during the event (also known as continue mode of operation) to assess drive
behaviour prediction during balanced and unbalanced sags. In particular, the models calculate the dc-link voltage and ac line
current dynamic evolution, assuming that neither the drive nor the system protection will trip. The comparison reveals minor
differences in behaviour between the three models and the actual drive, although the constant current model exhibits slightly
a better agreement. To verify whether differences in the simplified models remain small, extensive ranges of sags are
simulated, and drive sensitivity to sag type and depth is illustrated. As the straightforward models studied predict the
measured drive dynamic behaviour in severe network conditions with similar accuracy to other unnecessarily complicated
models, they are very useful to reduce computational burden and overall complexity for sag immunity as well as dynamic and
steady-state network studies. On the other hand, laboratory measurements on the actual drive when the inertia ride-through
mode of operation is active illustrate that the simplified models are not valid when the inverter control strategy is modified
during the sag.
CitationBogarra, S. [et al.]. Comparison of simplified models for voltage-source-inverter-fed adjustable-speed drive during voltage sags when the during-event continue mode of operation is active. "IET electric power applications", 13 Novembre 2014, vol. 8, núm. 9, p. 329-341.
ISSN1751-8660
Files | Description | Size | Format | View |
---|---|---|---|---|
Comparison.pdf | ARTICLE | 1,243Mb | Restricted access |