Mostra el registre d'ítem simple

dc.contributor.authorRiba Ruiz, Jordi-Roger
dc.contributor.authorBogarra Rodríguez, Santiago
dc.contributor.authorGómez Pau, Álvaro
dc.contributor.authorMoreno Eguilaz, Juan Manuel
dc.contributor.otherUniversitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica
dc.contributor.otherUniversitat Politècnica de Catalunya. Departament d'Enginyeria Electrònica
dc.date.accessioned2020-06-03T07:23:08Z
dc.date.available2020-06-03T07:23:08Z
dc.date.issued2020-06-01
dc.identifier.citationRiba, J. [et al.]. Experimental study of the corona performance of aged sand-cast substation connectors. "Energies", 1 Juny 2020, vol. 13, núm. 11, p. 1-13.
dc.identifier.issn1996-1073
dc.identifier.urihttp://hdl.handle.net/2117/189794
dc.description.abstractSubstation connectors, like many other high-voltage products, are tested once manufactured. However, the corona behavior of aged specimens can differ from that exhibited by newer ones, thus generating detrimental technical and environmental effects. Manufacturers need to know the long-term corona behavior of substation connectors to offer their customers maximum safety and transparency about such critical products. This paper analyzes the ageing effect on the surface roughness and the visual corona extinction voltage of sand-cast aluminum connectors, which were artificially aged in a salt spray chamber for different periods. The experimental results show an important variability of the surface roughness and corona extinction voltage (CEV) among connectors with the same ageing level due to the sand-casting manufacturing process. The results in this paper also show a slight increase in the surface roughness with the ageing period, although there is not a clear pattern between the applied ageing level and the experimental CEV value. It is concluded that the inherent variability among connectors due to the sand-cast process has more influence than the ageing effect itself.
dc.description.sponsorshipThis research was partially funded by Ministerio de Ciencia e Innovación de España, grant number RTC-2017-6297-3 and by the Generalitat de Catalunya, grant number 2017 SGR 967.
dc.format.extent13 p.
dc.language.isoeng
dc.rightsAttribution 3.0 Spain
dc.rights.urihttp://creativecommons.org/licenses/by/3.0/es/
dc.subjectÀrees temàtiques de la UPC::Enginyeria elèctrica::Alta tensió
dc.subject.lcshHigh voltages
dc.subject.lcshElectric conductors
dc.subject.lcshSand
dc.subject.otherCorona effect
dc.subject.otherAgeing
dc.subject.otherSubstation connectors
dc.subject.otherHigh-voltage
dc.subject.otherSand casting
dc.titleExperimental study of the corona performance of aged sand-cast substation connectors
dc.typeArticle
dc.subject.lemacAlta tensió
dc.subject.lemacConductors elèctrics
dc.subject.lemacSorra
dc.contributor.groupUniversitat Politècnica de Catalunya. MCIA - Motion Control and Industrial Applications Research Group
dc.contributor.groupUniversitat Politècnica de Catalunya. QSE - Qualitat del Subministrament Elèctric
dc.identifier.doi10.3390/en13112785
dc.description.peerreviewedPeer Reviewed
dc.relation.publisherversionhttps://www.mdpi.com/1996-1073/13/11/2785/htm
dc.rights.accessOpen Access
local.identifier.drac28600264
dc.description.versionPostprint (published version)
dc.relation.projectidinfo:eu-repo/grantAgreement/MICINN/2PE/RTC-2017-6297-3
dc.relation.projectidinfo:eu-repo/grantAgreement/AGAUR/2PE/2017 SGR 967
local.citation.authorRiba, J.; Bogarra, S.; Gómez-Pau, Á.; Moreno-Eguilaz, J.M.
local.citation.publicationNameEnergies
local.citation.volume13
local.citation.number11
local.citation.startingPage1
local.citation.endingPage13


Fitxers d'aquest items

Thumbnail

Aquest ítem apareix a les col·leccions següents

Mostra el registre d'ítem simple