A novel voltage sag approach during unintentional islanding scenarios: A survey from real recorded events
View/Open
Cita com:
hdl:2117/176472
Document typeArticle
Defense date2019-07
Rights accessOpen Access
Except where otherwise noted, content on this work
is licensed under a Creative Commons license
:
Attribution-NonCommercial-NoDerivs 3.0 Spain
Abstract
In this paper, a new voltage sag approach is analytically modelled and validated using both simulation and field measurements. The main aspect of this approach is to propose a new voltage sag feature which appears during unintentional islanding operations (IOs). The unintentional IO occurs when an induction motor is removed from the main utility following a circuit breaker (CB) clearing, transiently, the induction motors (IMs) are acting as generators maintaining the affected distribution feeder with voltage until it is reconnected. The voltage sag modelled in the current article follows an exponential form, as a matter of fact, here it will be demonstrated that the proposed model reaches satisfactorily the field measurements and evidences the dependability of the model adopted. Furthermore, it is worthwhile to note that this novel power quality (PQ) event has not been investigated yet and enhances voltage sag studies. Lastly, it is crucial to point out that all recorded events and a large amount of data needed so as to validate this transient, has been measured in a distribution network (DN) located in Spain.
CitationSerrano, A.; Casals, P.; Bosch, R. A novel voltage sag approach during unintentional islanding scenarios: A survey from real recorded events. "Renewable energy and power quality journal", Juliol 2019, vol. 17, p. 43-48.
ISSN2172-038X
Publisher versionhttp://www.icrepq.com/RE&PQJ-papers.html
Files | Description | Size | Format | View |
---|---|---|---|---|
215-19-Serrano_Casals_Bosch_RevistaRE&PQJ.pdf | Artículo Revista | 1,742Mb | View/Open |