Mostra el registre d'ítem simple

dc.contributor.authorSchönleber, Kevin
dc.contributor.authorPrieto Araujo, Eduardo
dc.contributor.authorRatés Palau, Sergi
dc.contributor.authorGomis Bellmunt, Oriol
dc.contributor.otherUniversitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica
dc.date.accessioned2017-11-24T08:19:57Z
dc.date.available2017-11-24T08:19:57Z
dc.date.issued2017-11
dc.identifier.citationSchönleber, K., Eduardo Prieto-Araujo, Ratés, S., Gomis-Bellmunt, O. Handling of unbalanced faults in HVDC-connected wind power plants. "Electric power systems research", Novembre 2017, vol. 152, p. 148-159.
dc.identifier.issn0378-7796
dc.identifier.urihttp://hdl.handle.net/2117/111143
dc.description.abstractHigh-voltage DC (HVDC) connections enable integration of wind power plants located very far from shore. The decoupled AC offshore grid comprises multiple WT converters, and the voltage magnitude and frequency is primarily controlled by the offshore high-voltage DC voltage-source converter (VSC-HVDC). Faults in the offshore grid challenge the connected converters to provide an adequate response improving the overall fault behavior. Of special interest are asymmetrical faults due to the resulting unbalanced voltage conditions. This article addresses such conditions in the offshore grid and analyzes the impact on the offshore grid behavior for different converter contributions. Four fault ride-through strategies are studied for the WT converters. The effect of over-modulation of the converter voltages during such voltage conditions is highlighted. A test system is defined to analyze the fault and post-fault behavior. It is found that voltage support from the WT converters in both positive and negative sequence shows the best performance compared to controlled negative sequence current suppression. This scheme helps additionally the VSC-HVDC AC voltage control to return quickly to normal operation. To validate this statement simulations are performed for line-to-line (LL) and single line-to-ground (SLG) faults in immediate vicinity of the VSC-HVDC.
dc.format.extent12 p.
dc.language.isoeng
dc.subjectÀrees temàtiques de la UPC::Enginyeria elèctrica
dc.subject.lcshWind power plants
dc.subject.otherFault-ride through
dc.subject.otherHigh voltage direct current (HVDC)
dc.subject.otherOffshore grid control
dc.subject.otherVoltage-source converter
dc.subject.otherWind power plants
dc.titleHandling of unbalanced faults in HVDC-connected wind power plants
dc.typeArticle
dc.subject.lemacEnergia eòlica
dc.contributor.groupUniversitat Politècnica de Catalunya. CITCEA - Centre d'Innovació Tecnològica en Convertidors Estàtics i Accionaments
dc.identifier.doi10.1016/j.epsr.2017.06.026
dc.description.peerreviewedPeer Reviewed
dc.relation.publisherversionhttp://www.sciencedirect.com/science/article/pii/S0378779617302754?via%3Dihub
dc.rights.accessOpen Access
local.identifier.drac21547707
dc.description.versionPostprint (author's final draft)
local.citation.authorSchönleber, K.; Prieto-Araujo, Eduardo; Ratés, S.; Gomis-Bellmunt, O.
local.citation.publicationNameElectric power systems research
local.citation.volume152
local.citation.startingPage148
local.citation.endingPage159