Saturation temperature effects on heat transfer performance of a falling film evaporator using enhanced tubes
Visualitza/Obre
Estadístiques de LA Referencia / Recolecta
Inclou dades d'ús des de 2022
Cita com:
hdl:2099.1/14572
Tutor / directorThome, J.R.
Tipus de documentProjecte/Treball Final de Carrera
Data2010
Condicions d'accésAccés obert
Tots els drets reservats. Aquesta obra està protegida pels drets de propietat intel·lectual i
industrial corresponents. Sense perjudici de les exempcions legals existents, queda prohibida la seva
reproducció, distribució, comunicació pública o transformació sense l'autorització del titular dels drets
Abstract
In this work, the existing LTCM falling lm facility was utilized to perform
falling lm evaporation measurements on a vertical row of horizontal tubes.
The enhanced boiling tube, Wolverine Turbo-B5, was tested using R-134a
and R-236fa. The tests were carried out at di erent saturation temperatures
of: 7.5 C, 10 C, 12.5 C, 15 C, 17.5 C, 20 C, 22.5 C, 25 C, 27.5 C and 30 C
adding them to the existing 5 C saturation temperature in the database
from previous work. All the tests were carried out with liquid lm Reynolds
numbers ranging from 0 to 3000, and nominal heat
uxes of 20, 40 and
60 kW/m2. The experimental results for all temperatures are compared
with the current prediction method of Christians (2010). The e ects of
the di erent saturation temperatures on the heat transfer coe cient were
analyzed and compared for R-134a and R-236fa. Pool boiling heat transfer
coe cients were measured in the LTCM pool boiling facility to obtain the
falling lm multiplier Kff (Falling lm heat transfer coe cient relative to
pool boiling coe cient at the same heat
ux). These tests were carried out
at 20 C and 30 C for both R-134a and R-236fa. Finally an uncertainty
analysis of the refrigerant lm Reynolds number was carried out in order
to quantify the error in its calculation and a new lter for the experimental
data was proposed.
TitulacióENGINYERIA INDUSTRIAL (Pla 1994)
Fitxers | Descripció | Mida | Format | Visualitza |
---|---|---|---|---|
Andreu_Alonso_Master_Thesis_LTCM.pdf | Report | 3,902Mb | Visualitza/Obre |