Analyzing the effect of corona losses on dynamic line rating models for overhead transmission lines

Carregant...
Miniatura
El pots comprar en digital a:
El pots comprar en paper a:

Projectes de recerca

Unitats organitzatives

Número de la revista

Títol de la revista

ISSN de la revista

Títol del volum

Col·laborador

Editor

Tribunal avaluador

Realitzat a/amb

Tipus de document

Article

Data publicació

Editor

Elsevier

Condicions d'accés

Accés obert

item.page.rightslicense

Creative Commons
Aquesta obra està protegida pels drets de propietat intel·lectual i industrial corresponents. Llevat que s'hi indiqui el contrari, els seus continguts estan subjectes a la llicència de Creative Commons: Reconeixement 4.0 Internacional

Assignatures relacionades

Assignatures relacionades

Publicacions relacionades

Datasets relacionats

Datasets relacionats

Projecte CCD

Abstract

High-voltage transmission lines tend to generate corona activity. The value of corona losses is highly dependent on several parameters such as line configuration, conductor geometry, surface condition, operating voltage and weather conditions. International guidelines and standards such as Cigré, IEEE and IEC recommend that corona losses should not be considered when developing thermal conductor models, so such losses are typically omitted when developing dynamic line rating (DLR) applications. DLR is a set of techniques based on dynamically changing the thermal ratings of transmission lines based on changes in environmental conditions (wind, temperature, etc.). To develop accurate DLR models that include corona losses, a large amount of line data is required, including operating voltage, complete conductor information (materials, dimensions, etc.), bundle and line geometry, phase layout, and ground clearance, among others. To validate the accuracy of such models, part of the complete line data, long-term measurements of instantaneous corona losses in existing lines, operating voltage and weather conditions are required. However, the development of DLR approaches and the inclusion of corona losses in such models is severely limited by the lack of experimental work that includes a complete description of all this information. Based on experimental corona losses already published in the literature, this paper uses an accurate conductor model that accounts for radial heat transfer to show that, under certain conditions, corona losses are comparable to and even greater than Joule losses, which are usually the main source of conductor heating, suggesting that corona losses should be included in the development of accurate thermal conductor models. It has also been shown that for conductors in a normal condition, operating in fair weather conditions and at rated line load, corona losses are typically less than 2% of the Joule losses, resulting in a reduction of the maximum current carrying capacity of less than 1%. However, for heavily contaminated conductors, the reduction in current carrying capacity due to the effect of corona losses can be as high as 15%.

Descripció

Persones/entitats

Document relacionat

Versió de

Citació

Riba, J.; Moreno-Eguilaz, J.M. Analyzing the effect of corona losses on dynamic line rating models for overhead transmission lines. "International journal of electrical power & energy systems", Maig 2025, vol. 166, núm. article 110546.