dc.contributor.authorCapelli, Francesca
dc.contributor.authorRiba Ruiz, Jordi-Roger
dc.contributor.authorPérez, Joan
dc.contributor.otherUniversitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica
dc.date.accessioned2016-06-13T13:20:03Z
dc.date.available2016-06-13T13:20:03Z
dc.date.issued2016-05-30
dc.identifier.citationCapelli, F., Riba, J., Pérez, J. Three-dimensional finite-element analysis of the short-time and peak withstand current tests in substation connectors. "Energies", 30 Maig 2016, vol. 9, núm. 418, p. 1-16.
dc.identifier.issn1996-1073
dc.identifier.urihttp://hdl.handle.net/2117/87925
dc.description.abstractPower devices intended for high-voltage systems must be tested according to international standards, which includes the short-time withstand current test and peak withstand current test. However, these tests require very special facilities which consume huge amounts of electrical power. Therefore, mathematical tools to simulate such tests are highly appealing since they allow reproducing the electromagnetic and thermal behavior of the test object in a fast and economical manner. In this paper, a three-dimensional finite element method (3D-FEM) approach to simulate the transient thermal behavior of substation connectors is presented and validated against experimental data. To this end, a multiphysics 3D-FEM method is proposed, which considers both the connector and the reference power conductors. The transient and steady-state temperature profiles of both the conductors and connector provided by the 3D-FEM method prove its suitability and accuracy as compared to experimental data provided by short-circuit tests conducted in two high-current laboratories. The proposed simulation tool, which was proven to be accurate and realistic, may be particularly useful during the design and optimization phases of substation connectors since it allows anticipating the results of mandatory laboratory tests.
dc.format.extent16 p.
dc.language.isoeng
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/3.0/es/
dc.subjectÀrees temàtiques de la UPC::Enginyeria electrònica
dc.subjectÀrees temàtiques de la UPC::Energies::Energia elèctrica
dc.subject.lcshElectric substations--Testing
dc.subject.otherfinite element method
dc.subject.othershort-time withstand current test
dc.subject.otherpeak withstand current test
dc.subject.othersimulation
dc.subject.othersubstation
dc.subject.otherconnector
dc.titleThree-dimensional finite-element analysis of the short-time and peak withstand current tests in substation connectors
dc.typeArticle
dc.subject.lemacSubestacions elèctriques--Proves
dc.contributor.groupUniversitat Politècnica de Catalunya. MCIA - Motion Control and Industrial Applications Research Group
dc.identifier.doi10.3390/en9060418
dc.description.peerreviewedPeer Reviewed
dc.relation.publisherversionhttp://www.mdpi.com/1996-1073/9/6/418
dc.rights.accessOpen Access
local.identifier.drac18548883
dc.description.versionPostprint (published version)
local.citation.authorCapelli, F.; Riba, J.; Pérez, J.
local.citation.publicationNameEnergies
local.citation.volume9
local.citation.number418
local.citation.startingPage1
local.citation.endingPage16