Mostra el registre d'ítem simple

dc.contributor.authorCubí Montanyà, Eduard
dc.contributor.authorSalom Tormo, Jaume
dc.contributor.authorGarrido Soriano, Núria
dc.contributor.otherUniversitat Politècnica de Catalunya. Departament de Màquines i Motors Tèrmics
dc.date.accessioned2015-04-07T12:17:18Z
dc.date.available2016-02-15T01:30:26Z
dc.date.created2015-02-13
dc.date.issued2015-02-13
dc.identifier.citationCubi, E.; Salom, J.; Garrido, N. Energy-efficient ventilation control strategies for surgery rooms. "Science and Technology for the Built Environment", 13 Febrer 2015, vol. 21, núm. 2, p. 228-237.
dc.identifier.issn2374-474X
dc.identifier.urihttp://hdl.handle.net/2117/27138
dc.description.abstractSurgery room specific energy use is among the highest in the built environment due to stringent indoor environmental quality and infection control requirements. This study uses a calibrated energy model to evaluate the environmental and economic performance of a variety of ventilation control strategies that reduce surgery room energy use while maintaining indoor environmental quality and infection control performance. The individual control strategies evaluated in this study are (1) temperature and relative humidity reset, (2) air recirculation, (3) airflow reset, and (4) particle concentration based airflow control. Combinations of these strategies are also evaluated. The best performing combinations of control strategies can reduce surgery room primary energy use, CO2 emissions, and energy costs by up to 86% relative to the standard practice. Temperature and relative humidity reset is the strategy that offers the largest benefits. Particle concentration based airflow control shows modest results partly due to the conservative infection control performance target. Future research should define infection control performance thresholds during operation.
dc.format.extent10 p.
dc.language.isoeng
dc.publisherTaylor & Francis
dc.subjectÀrees temàtiques de la UPC::Edificació::Instal·lacions i acondicionament d’edificis::Instal·lacions de ventilació
dc.subjectÀrees temàtiques de la UPC::Energies::Eficiència energètica
dc.subject.lcshHospitals -- Energy conservation
dc.subject.otherEnergy efficiency
dc.subject.otherSurgery rooms
dc.subject.otherRequirements
dc.subject.otherSimulation model
dc.titleEnergy-efficient ventilation control strategies for surgery rooms
dc.typeArticle
dc.subject.lemacHospitals -- Estalvi d'energia
dc.subject.lemacVentilació -- Aparells i accessoris
dc.contributor.groupUniversitat Politècnica de Catalunya. SUMMLab - Sustainability Measurement and Modeling Lab
dc.identifier.doi10.1080/23744731.2014.992708
dc.description.peerreviewedPeer Reviewed
dc.rights.accessOpen Access
local.identifier.drac15540899
dc.description.versionPostprint (author’s final draft)
local.citation.authorCubi, E.; Salom, J.; Garrido, N.
local.citation.publicationNameScience and Technology for the Built Environment
local.citation.volume21
local.citation.number2
local.citation.startingPage228
local.citation.endingPage237


Fitxers d'aquest items

Thumbnail

Aquest ítem apareix a les col·leccions següents

Mostra el registre d'ítem simple