Mostra el registre d'ítem simple

dc.contributor.authorBanna, Hasan UI
dc.contributor.authorLuna Alloza, Álvaro
dc.contributor.authorYing, Shaoqing
dc.contributor.authorGhorbani, Hamidreza
dc.contributor.authorRodríguez Cortés, Pedro
dc.contributor.otherUniversitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica
dc.date.accessioned2015-02-11T12:14:23Z
dc.date.created2014
dc.date.issued2014
dc.identifier.citationBanna, H. [et al.]. Impacts of wind energy in-feed on power system small signal stability. A: IEEE International Conference on Renewable Energy Research and Applications. "Proceedings ICRERA 2014". Milwakuee: 2014, p. 615-622.
dc.identifier.urihttp://hdl.handle.net/2117/26302
dc.description.abstractIntegration of large amount of wind energy in an interconnected power system creates concerns about secure, reliable and economical operation of the entire power system. So it becomes very necessary to investigate the impacts of wind power infeed on the dynamic behavior of the power system. This paper presents the impacts of large amount of wind power in feed on the rotor oscillatory stability. Wind turbine generator types currently employed in wind farms, optimal location of the wind farms in the interconnected power system, reliable optimal dispatch of the wind power and the degree of tie line congestion have been thoroughly investigated. Kundur's two area network model has been utilized to study the mentioned impacts on the overall system using MATLAB/Simulink. Some of the key results show that the damping characteristics of the wind farms critically depend on the location of interconnection in the network and the optimal wind energy dispatch. Increasing the penetration of the wind energy generally improves the damping of the inter area oscillations. Moreover, reducing stress on the weak tie lines also improves the inter area mode of oscillation. So with the investigation of these impacts this study is helpful for the planning of new wind power projects.
dc.format.extent8 p.
dc.language.isoeng
dc.subjectÀrees temàtiques de la UPC::Energies::Energia eòlica::Aerogeneradors
dc.subjectÀrees temàtiques de la UPC::Energies::Energia elèctrica::Automatització i control de l’energia elèctrica
dc.subject.lcshWind turbines
dc.subject.lcshWind power plants
dc.subject.lcshRotors--Vibration
dc.subject.lcshDamping (Mechanics)
dc.subject.otherWind Farm Integration
dc.subject.otherWind Turbine Generators
dc.subject.otherRotor oscillatory stability
dc.subject.otherWind Power Location
dc.titleImpacts of wind energy in-feed on power system small signal stability
dc.typeConference report
dc.subject.lemacAerogeneradors -- Aerodinàmica
dc.subject.lemacAmortiment (Mecànica)
dc.subject.lemacRotors -- Vibració
dc.subject.lemacParcs eòlics
dc.contributor.groupUniversitat Politècnica de Catalunya. SEER - Sistemes Elèctrics d'Energia Renovable
dc.identifier.doi10.1109/ICRERA.2014.7016459
dc.description.peerreviewedPeer Reviewed
dc.rights.accessRestricted access - publisher's policy
local.identifier.drac15428887
dc.description.versionPostprint (published version)
dc.date.lift10000-01-01
local.citation.authorBanna, H.; Luna, A.; Ying, S.; Ghorbani, H.; Rodriguez, P.
local.citation.contributorIEEE International Conference on Renewable Energy Research and Applications
local.citation.pubplaceMilwakuee
local.citation.publicationNameProceedings ICRERA 2014
local.citation.startingPage615
local.citation.endingPage622