Abstract
In this brief two sliding mode control alternatives
to regulate the stator voltage amplitude for a stand alone wound
rotor synchronous generator are presented. Both controllers use
the stator voltage -component error in the sliding surface. In
a first case an outer proportional-integral (PI) loop controller is
added to provide the proper d-voltage component reference. The
second approach consists in extending the dynamic system to include
the integral term as state variable and to modify the former
sliding surface by adding this new state. Finally, both simulations
and experimental results validates the proposed algorithms
CitacióDoria-Cerezo, A. [et al.]. Control of a Stand-Alone Wound Rotor Synchronous Generator: Two Sliding Mode Approaches via Regulation of the d-Voltage Component. "IEEE transactions on control systems technology", 16 Maig 2011.
ISSN1063-6536
Col·leccions
- ACES - Control Avançat de Sistemes d'Energia - Articles de revista [194]
- Departament d'Enginyeria de Sistemes, Automàtica i Informàtica Industrial - Articles de revista [1.395]
- SEER - Sistemes Elèctrics d'Energia Renovable - Articles de revista [143]
- Departament d'Enginyeria Elèctrica - Articles de revista [884]
Fitxers | Descripció | Mida | Format | Visualitza |
---|---|---|---|---|
05767530.pdf | Article | 1,020Mb | Visualitza/Obre |