Citació: Casas, Joan R.; Aparicio, A. Rain-wind-induced cable vibrations in the Alamillo cable-stayed bridge (Sevilla, Spain): assessment and remedial action. "Structure and infrastructure engineering", Octubre 2010, vol. 6, núm. 5, p. 549-556.
Títol: Rain-wind-induced cable vibrations in the Alamillo cable-stayed bridge (Sevilla, Spain): assessment and remedial action
Autor: Casas Rius, Joan Ramon Veure Producció científica UPC; Aparicio Bengoechea, Ángel Carlos Veure Producció científica UPC
Data: oct-2010
Tipus de document: Article
Resum: Rain combined with wind action provoking vibration has been observed in the longest stays of the Alamillo cablestayed bridge in Sevilla (Spain). The maximum displacements observed are in the order of magnitude of 0.5 m and have caused discomfort problems to the pedestrian circulation across the bridge. The paper shows the analytical and experimental studies carried out to analyse the possible solutions and also the steps developed to stop the vibration phenomenon. In 2004, a dynamic test in the cables was envisaged to measure the actual damping in the cables. It became clear that damping in the cables was very low and the solution required the installation of dampers. The damping devices had to be in accordance with the relevant aesthetic constraints of the structure. The installation of the damping devices took place during 2007. After the installation of the damping devices, a new dynamic test was carried out in February of 2008 to check if the level of damping introduced by the dampers was appropriate. During the tests performed in 2004, the natural frequencies of vibration were also obtained at the same time than damping. The comparison between the two sets of natural frequencies (1992 and 2004) allow to extract important conclusions about the correct performance and condition state of the bridge as well as the evolution of forces in the cables after 12 years of construction due to creep in the tower.
ISSN: 1573-2479
URI: http://hdl.handle.net/2117/7871
DOI: 10.1080/15732470903068607
Apareix a les col·leccions:TE - Tecnologia d´Estructures. Articles de revista
DEC - Departament d'Enginyeria de la Construcció. Articles de revista
Altres. Enviament des de DRAC
Comparteix:


Stats Mostra les estadístiques d'aquest ítem

SFX Query

Tots els drets reservats. Aquesta obra està protegida pels drets de propietat intel·lectual i industrial corresponents. Sense perjudici de les exempcions legals existents, queda prohibida la seva reproducció, distribució, comunicació pública o transformació sense l'autorització del titular dels drets.

Per a qualsevol ús que se'n vulgui fer no previst a la llei, dirigiu-vos a: sepi.bupc@upc.edu

 

Valid XHTML 1.0! Programari DSpace Copyright © 2002-2004 MIT and Hewlett-Packard Comentaris
Universitat Politècnica de Catalunya. Servei de Biblioteques, Publicacions i Arxius