E-prints UPC >
Altres >
Enviament des de DRAC >
Empreu aquest identificador per citar o enllaçar aquest ítem:
http://hdl.handle.net/2117/16633
|
Ítem no disponible en accés obert per decisió de l'autor/autora
| Arxiu |
Descripció |
Mida | Format |
| 0091.pdf | | 228.64 kB | Adobe PDF |  |
|
| Citació: | Casillas, M.; Garza, L.; Puig, V. Extended-horizon analysis of pressure sensitivities for leak detection in water distribution networks. A: IFAC International Symposium on Fault Detection, Supervision and Safety for Technical Processes. "8th SAFEPROCESS 2012. IFAC International Symposium on Fault Detection, Supervision and Safety for Technical Processes". Mexico City: IFAC, 2012, p. 570-575. |
| Títol: | Extended-horizon analysis of pressure sensitivities for leak detection in water distribution networks |
| Autor: | Casillas Ponce, Myrna Violeta; Garza Castañón, Luís Eduardo; Puig Cayuela, Vicenç  |
| Editorial: | IFAC |
| Data: | 2012 |
| Tipus de document: | Conference report |
| Resum: | In this paper, a new approach for leak detection in water networks is proposed which considers
an extended time horizon analysis of pressure sensitivities. Previous works based on pressure sensitivities
analysis were developed by considering time instant evaluation. This fact makes them very sensitive to
demand changes and noise in measurements. The proposed approach has been combined with five
detection methods: the first is the binarization method, the second, third and fourth are based on the
comparison of measured pressure vectors with leak sensitivity matrix using methods of correlation, vector
angle and Euclidean distance respectively. And, finally, the fifth is based on the least square optimization
method. Another contribution of this paper is the performance comparison between the five detection
methods in presence of single leaks in scenarios with noise in measurements and nodal demands. Results
showed that in most of the methods effectiveness is high, being the best the vector angle method, with
effectiveness higher than 96%. The correlation and optimization method had similar behaviors with
effectiveness superior to 90%. Finally, the binarization method is effective only in some scenarios but in
presence of noise has a poor performance. |
| ISBN: | 978-80-8075-477-8 |
| URI: | http://hdl.handle.net/2117/16633 |
| Apareix a les col·leccions: | Departament d'Enginyeria de Sistemes, Automàtica i Informàtica Industrial. Ponències/Comunicacions de congressos SAC - Sistemes Avançats de Control. Ponències/Comunicacions de congressos Altres. Enviament des de DRAC
|
| Comparteix: |
|
Queda prohibida la reproducció, transformació, distribució i comunicació pública d'aquesta obra. Es permet, en tot cas, la reproducció per a ús privat sempre i quan la còpia que se'n faci no sigui objecte d'utilització col·lectiva ni lucrativa (art. 31.2 del Reial Decret Legislatiu 1/1996, de 12 d'abril, pel qual s'aprova el Text Refós de la Llei de Propietat Intel·lectual, http://bibliotecnica.upc.es/sepi/legislacio.asp).
Per a qualsevol ús que es vulgui fer diferent al permès, dirigiu-vos a: sepi@upc.edu
|