| Citació: | Castilla, M. [et al.]. Grid-fault control scheme for three-phase photovoltaic inverters with adjustable power quality characteristics. "IEEE transactions on power electronics", 23 Desembre 2010, vol. 25, núm. 12, p. 2930-2940. |
| Títol: | Grid-fault control scheme for three-phase photovoltaic inverters with adjustable power quality characteristics |
| Autor: | Castilla Fernández, Miguel ; Miret Tomàs, Jaume ; Sosa Avendaño, Jorge Luis ; Matas Alcalá, José ; García de Vicuña Muñoz de la Nava, José Luis  |
| Data: | 23-des-2010 |
| Tipus de document: | Article |
| Resum: | The power quality of a three-phase photovoltaic (PV)
inverter drastically deteriorates in the presence of grid faults with
unbalanced voltages.Aripple in the injected power and an increase
in the current harmonic distortion are the main noticeable adverse
effects produced by this abnormal grid situation. Several grid-fault
control schemes are nowadays available for operating under unbalanced
grid voltage. These control schemes usually have extreme
power quality characteristics. Some of them have been conceived
to completely avoid power ripple during unbalanced voltage sags,
but at an expense of high current harmonic distortion.With other
schemes, the harmonic distortion is totally eliminated but at an
expense of high ripple in the injected power. This paper further
explores the performance of PV inverters under unbalanced voltage
sags. It has three theoretical contributions: 1) a generalized
control scheme, which includes the aforementioned grid-fault controllers
as particular cases; 2) a control strategy based on the use
of continuous values for the control parameters. This original approach
gives adjustable power quality characteristics that cannot
be achieved with the previous control schemes; 3) three different
control algorithms for calculating the continuous values of the control
parameters. These contributions are experimentally validated
with a digital signal processor-based laboratory prototype. |
| ISSN: | 0885-8993 |
| URI: | http://hdl.handle.net/2117/11555 |
| Versió de l'editor: | 10.1109/TPEL.2010.2070081 |
| Versió de l'editor: | http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=5560869&tag=1 |
| Apareix a les col·leccions: | Altres. Enviament des de DRAC Departament d'Enginyeria Elèctrica. Articles de revista Departament d'Enginyeria Electrònica. Articles de revista SEPIC - Sistemes Electrònics de Potència i de Control. Articles de revista
|
| Comparteix: |
|
Queda prohibida la reproducció, transformació, distribució i comunicació pública d'aquesta obra. Es permet, en tot cas, la reproducció per a ús privat sempre i quan la còpia que se'n faci no sigui objecte d'utilització col·lectiva ni lucrativa (art. 31.2 del Reial Decret Legislatiu 1/1996, de 12 d'abril, pel qual s'aprova el Text Refós de la Llei de Propietat Intel·lectual, http://bibliotecnica.upc.es/sepi/legislacio.asp).